日本黄色视频在线免费网站|xxxx日本真实自拍一卡|亚州AV无码永久无限精品|琪琪精品视频在线播放免费

EPC Products Material Testing Equipment Fire Testing Reaction to Fire Tests Test Method for Evaluating Thermal Runway Fire Propagation in Battery Energy Storage Systems
產(chǎn)品中心
Test Method for Evaluating Thermal Runway Fire Propagation in Battery Energy Storage Systems

Model:UL 9540A

Use:Test Method for Evaluating Thermal Runway Fire Propagation in Battery Energy Storage Systems. The primary measurement is heat release rate using oxygen consumption calorimetry which is core to FTT’s product range and expertise.

Standard:UL 9540A

Related Products

Introduction of the Test Method for Evaluating Thermal Runway Fire Propagation in Battery Energy Storage Systems

 

FTT UL 9540A Test

FTT supplies and installs the UL 9540A and trains clients in its use. FTT can also supply any specific components to clients wishing to part design and build their own equipment.

 

The UL 9540A standard has been developed to test battery energy storage systems in different scales: 

? Cell level
? Module level
? Unit level
? Installation level 

 

The Cell Level Test

The cell level test involves heating up a battery cell to initiate thermal runaway. Flexible film heaters are applied to the external of a battery and connected to a temperature controller. The Cell Level Test primarily uses analytical chemistry apparatus and is not a reaction-to-fire test. Consequently, clients source this apparatus themselves so it is not offered by FTT.

 

The Module Level Test

The module level test involves heating up several cells in a battery module to initiate thermal runaway and collecting the gaseous products under a hood and exhaust system with an internal diameter of 400 mm. A sample of the exhaust gas is taken to measure the concentration of oxygen, carbon dioxide, carbon monoxide, hydrocarbons and hydrogen as well as the composition of additional gases using FTIR. In addition the concentration of smoke in the exhaust is measured using a white light smoke measurement system. These measurements enable, among others, the heat release to be determined by the technique known as oxygen consumption calorimetry and smoke production rates to be determined by the FTT Calorimetry software (BatteryCalc).

 

There are several parts to the Module Level test setup:

? Extraction system 

? Weighing system 

? Thermal runaway initiation system 

? Temperature measurement system

? Heat release and smoke production instrumentation

? Instrumentation to calibrate the heat release rate system

? Additional gas measurements 

? Data acquisition and analysis software

 


The Unit Level Test

The testing principle from the module level test can be applied to the unit level test measuring fires up to 10MW by increasing the hood size, exhaust diameter and exhaust flow rate, as explained in ISO 24473, Open Calorimetry – Measurement of the rate of production of heat and combustion products for fires up to 40MW.

The unit level test involves heating up several cells in a battery energy storage system (BESS) to initiate thermal runaway and collecting the gaseous products under a hood and exhaust system with an internal diameter of 1.524m (in order to measure heat release rates up to 10MW). A sample of the gases in the exhaust are analysed for the concentration of oxygen, carbon dioxide, carbon monoxide and hydrocarbons as well as the composition of additional gases using FTIR. In addition the amount of smoke in the exhaust is measured using a white light smoke measurement system. The environment around the BESS is instrumented in order to measure the temperature and heat flux at adjacent walls and secondary BESS systems.

 

There are several parts to the Unit Level test setup:

? Heat release and smoke production instrumentation

? Instrumentation to calibrate the heat release rate system

? Extraction system

? Additional gas measurements

? Thermal runaway initiation system

? Temperature measurement systems

? Heat flux measurement system

? Convective heat release rate measurement system

 


The Installation Level Test

Installation level tests are only required for non-residential installations. The test configuration is similar to the Unit Level test, but does not measure the heat release and smoke production rates.

The installation level test involves heating up several cells in a battery energy storage system (BESS) to initiate thermal runaway in a room which contains a sprinkler system or other fire and explosion mitigation methods. A sample of the gases in the room is taken and analyzed for the concentration of hydrocarbons and hydrogen as well as the composition of additional gases using FTIR. The environment around the BESS is instrumented in order to measure the temperature and heat flux at adjacent walls and secondary BESS systems.

 

There are several parts to the Installation Level test setup:

? Extraction system

? Gas measurements

? Thermal runaway initiation system

? Temperature measurement systems

? Heat flux measurement system


Project Case
Solution
Download
相關(guān)標(biāo)簽
Battery, test method, energy storage, thermal runaway, 9540A, module, unit, installation
主站蜘蛛池模板: 从江县| 荥经县| 遵化市| 成武县| 鲁甸县| 安岳县| 许昌县| 东港市| 衡水市| 肇东市| 从江县| 宁波市| 无为县| 墨脱县| 新兴县| 苏尼特左旗| 务川| 五指山市| 志丹县| 扎兰屯市| 阆中市| 深泽县| 平泉县| 平舆县| 农安县| 博罗县| 武山县| 京山县| 仁化县| 宁明县| 甘德县| 赤峰市| 化德县| 邢台县| 太仆寺旗| 鹤庆县| 合山市| 石渠县| 米林县| 潍坊市| 岗巴县|